This is a Medium Voltage laboratory that has two independent test spaces, each with a useful test development area of over 50 m2 and an independent control office to have visual contact with the test area to avoid any risk to people. Laboratory capacities: -Direct connection to the 30 kV distribution network -Development of 4 MVA with (1) 15 Vac levels between 690 V and 4780 V, and (2) Vdc between 930 V and 6450 V. -2MVA and 3MVA VRT generators. -2MVA motor and drive converter.
Immersive systems and digital twin for power infrastructures
Integration of distributed generation and storage. Microgrids
Optimal grid operation and demand management
Product validation (HW/SW) for electricity grids
690 Vac VRT generators between 2 MVA and 3 MVA
LVRT capacity up to 0 pu of 2 MVA and HVRT capacity up to 1.5 pu of 3 MVA
A drive motor with power converter to regulate the driving torque
2 MVA power motor to regulate the driving torque
Electromechanical protection and switching systems
Three cells (600 A/30 kV) in SF6, three ac switches (one 1200 A/12 kV in SF6 and two 1200 A/ 690 V), eight contactors (five 600 A/4000 V and three 200 A/4000 V)
Several ABB dry transformers
Dyn11 of powers between 1 MVA and 2.6 MVA at 30 kV/690 V
Two Alkargo silicone transformers
2 MVA 30 kV/2x690 V open D-secondary (two independent open D-secondary windings at the secondary). Together with a busbar cabinet, they are used to generate the 15 voltage levels mentioned in the description.
Characterization and testing of different semiconductor technologies (Si, SiC, GaN) for medium voltage applications.
Transient analysis and validation of electrical machines and transformers for distribution networks with the capacity to develop powers up to 4 MVA and voltages up to 4780 Vac and 6500 Vdc. Technical support from specialized personnel is offered
Analysis and validation of power electronic equipment and prototypes capable of developing power ratings up to 4 MVA and voltages up to 4780 Vac and 6500 Vdc. Technical support from specialized personnel is offered
Validation and testing of insulation capacities of cables, transformers and devices requiring medium voltage insulation.